General specifications
|
Signal type
|
Analog input
|
Supply
|
Connection
|
terminals 14+, 15- or power feed module/Power Rail
|
Rated voltage
|
20 ... 30 V DC
|
Ripple
|
within the supply tolerance
|
Power dissipation/power consumption
|
≤ 0.98 W / 0.98 W
|
Input
|
Connection
|
terminals 1, 2, 3, 4
|
RTD
|
type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
|
|
Measuring current
|
approx. 200 μA with RTD
|
|
Types of measuring
|
2-, 3-, 4-wire connection
|
|
Lead resistance
|
max. 50 Ω per line
|
|
Measuring circuit monitoring
|
sensor breakage, sensor short-circuit
|
Thermocouples
|
type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
|
|
Cold junction compensation
|
external and internal
|
|
Measuring circuit monitoring
|
sensor breakage
|
Potentiometer
|
0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
|
Voltage
|
selectable within the range -100 ... 100 mV
|
Input resistance
|
≥ 1 MΩ (-100 ... 100 mV)
|
Output
|
Connection
|
output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
|
Output
|
Analog current output
|
|
Current range
|
0 ... 20 mA or 4 ... 20 mA
|
|
Fault signal
|
downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
|
|
Source
|
load 0 ... 550 Ω
open-circuit voltage ≤ 18 V
|
|
Sink
|
Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω.
|